JANOS Help System: [Commands] [Topics] [Tech Support] [Printable Manual] [Search]
Results for: "Latching." ...found 11 topics (0.358 secs) 1. From the topic: control JMP Protocol Latching may be enabled for any of the digital inputs. This is a form of event capture which can be very useful in monitoring pulsed signals. A latching input may be set to trigger on either a positive going or negative going signal edge. In waiting for the event the input is considered to be armed. When the trigger signal is detected the input changes state. 2. From the topic: latching Latching Inputs Once latched a timer can be configured to reset the latch after a period suitable for the application. Alternatively the latch might hold the condition indefinitely until it is manually reset or acknowledged by the application programming. This may be appropriate in a fire alarm situation. 3. From the topic: IO/Inputs/[DIN]/Latching IO/Inputs/[DIN]/Latching Registry Key IO/Inputs/[DIN]/Latching 4. From the topic: debounce Debouncing Inputs Relays and switches have mechanical contacts which physically make or break a circuit. Rarely will the contacts come together solidly or separate decisively without bouncing (briefly making and breaking the circuit). This can raise havoc with digital latching and counting circuits that might be monitoring through the relay/switch contact. It can result in latching at the wrong time (when the relay opens for instance) or in extra counts. Both are undesirable. 5. From the topic: jrmon JRMON User Commands [R]eset NNN Digital Inputs may be latched. Depending on configuration these may reuire manual intervention to be reset or unlatched. The command 'r2' resets any active latching on Digital Input 2.