Usage Registry Key
NAME
IO/Outputs/[ROUT]/UsageState
DEFAULT
1 (CLOSED)
DESCRIPTION
This specifies whether usage time is accumulated when the relay is in the
CLOSED state (1) or in the OPEN state (0). The key is set to 1 or 0
respectively.
Note that certain relays may be reconfigured from Normally Open (NO) to
Normally Closed (NC) by jumper. This may affect the choice of metering
state.
ALARM ENABLE
IO/Outputs/[ROUT]/Usage/Alarm
DEFAULT
disabled
DESCRIPTION
Set to enable an alarm when the associated usage meter reaches the Limit
specified.
USAGE LIMIT
IO/Outputs/[ROUT]/Usage/Limit
DEFAULT
0.0
DESCRIPTION
Defines the alarm setpoint in hours and may include a fractional part. The
associated relay output goes into alarm when the usage meter reaches or
exceeds this setpoint.
EVENTS ENABLE
IO/Outputs/[ROUT]/Usage/OnAlarm
DEFAULT
disabled
DESCRIPTION
This key may be optionally defined to enable services related to Relay
Output Usage Alarms.
EMAIL ENABLE
IO/Outputs/[ROUT]/Usage/Email
DEFAULT
disabled
DESCRIPTION
This Registry key enables Usage Notification email.
CUSTOM EMAIL NOTIFICATION
IO/Outputs/[ROUT]/Usage/EmailBlock
DEFAULT
None
DESCRIPTION
This may be used define a block that creates a unique Usage Notification
message.
HOLDOFF
IO/Outputs/[ROUT]/Usage/HoldOff
DEFAULT
300000 (milliseconds)
DESCRIPTION
This defines the amount of time in milliseconds that the Relay Output usage
alarm must remain clear before any subsequent usage alarm on this input will
be acted upon. The default is 300000 or 5 minutes.
When an alarm occurs the services associated with that event are performed.
The alarm must reset and remain so for this amount of time before those
actions would be performed again.
SEE ALSO
HELP Topics:
EMAIL_BLOCK
[/flash/manpages/registry.hlp:3410]