IO/Inputs/[DIN]/Count/Multiplier Registry Key
NAME
IO/Inputs/[DIN]/Count/Multiplier
DEFAULT
0.0
DESCRIPTION
When the Count Multiplier is set to 0.0 (default) the absolute counter value
is displayed. When a non-zero multiplier is specified the value is used to
scale the counter value for display. The scaled counter value is also used
for count alarm trigger points.
Input pulses are counted and each count may represent some incremental value
of a quantity measured by the remote sensor. For instance each pulse might
indicate that 5 gallons of water has passed through a flow sensor. Im this
example you might set the multiplier IO/Inputs/[DIN]/Count/Multiplier to
5.0 and the reported units IO/Inputs/[DIN]/Count/Units to "Gallons". The
WebUI would then report the accumulated gallons as measured.
SEE ALSO
HELP Topics:
IO/Inputs/[DIN]/Count/SampleTime,
IO/Inputs/[DIN]/Count/Units
COUNTING,
DIN
[/flash/manpages/registry.hlp:3088]