JANOS Help System: [Commands] [Topics] [Tech Support] [Printable Manual] [Search]
Counter Alarm Email Registry Key EVENT ENABLE IO/Inputs/[DIN]/Alarm1/OnAlarm IO/Inputs/[DIN]/Alarm2/OnAlarm DEFAULT disabled DESCRIPTION Set this key to enable services related to the occurrence of Digital Input Counter Alarms on this input. HOLDOFF IO/Inputs/[DIN]/Alarm1/HoldOff IO/Inputs/[DIN]/Alarm2/HoldOff DEFAULT 300000 (milliseconds) DESCRIPTION This defines the amount of time in milliseconds that the Digital Input counter alarm must remain clear before any subsequent alarm on this input will be acted upon. The default is 300000 or 5 minutes. When an alarm occurs the services associated with that event are performed. The alarm must reset and remain so for this amount of time before those actions would be performed again. EMAIL ENABLE IO/Inputs/[DIN]/Alarm1/Email IO/Inputs/[DIN]/Alarm2/Email DEFAULT disabled DESCRIPTION This Registry key enables the Alarm Notification email. CUSTOM EMAIL NOTIFICATION IO/Inputs/[DIN]/Alarm1/EmailBlock IO/Inputs/[DIN]/Alarm2/EmailBlock DEFAULT None DESCRIPTION This may be used define a block that creates a unique Alarm Notification message. SEE ALSO HELP Topics: EMAIL_BLOCK, COUNTING, DIN [/flash/manpages/registry.hlp:3175]