Usage Registry Key
METERED STATE
IO/Inputs/[DIN]/UsageState
DEFAULT
1 (ON)
DESCRIPTION
This specifies whether usage time is accumulated with the input in the ON
state (1) or in the OFF state (0). The key is set to 1 or 0 respectively.
ALARM ENABLE
IO/Inputs/[DIN]/Usage/Alarm
DEFAULT
disabled
DESCRIPTION
Set this Registry key to enable an alarm when the associated usage meter
reaches a specified number of hours.
USAGE LIMIT
IO/Inputs/[DIN]/Usage/Limit
DEFAULT
0.0
DESCRIPTION
Defines the alarm setpoint in hours and fractions of hours. The associated
input goes into alarm when the usage meter reported by $HourMeter reaches
or exceeds this setpoint.
EVENTS ENABLE
IO/Inputs/[DIN]/Usage/OnAlarm
DEFAULT
disabled
DESCRIPTION
This key may be optionally defined to enable services related to Digital
Input Usage Alarms.
EMAIL ENABLE
IO/Inputs/[DIN]/Usage/Email
DEFAULT
disabled
DESCRIPTION
This Registry key enables Usage Notification email.
CUSTOM NOTIFICATION
IO/Inputs/[DIN]/Usage/EmailBlock
DEFAULT
None
DESCRIPTION
This may be used define a block that creates a unique Usage Notification
message.
HOLDOFF
IO/Inputs/[DIN]/Usage/HoldOff
DEFAULT
300000 (milliseconds)
DESCRIPTION
This defines the amount of time in milliseconds that the Digital Input usage
alarm must remain clear before any subsequent usage alarm on this input will
be acted upon. The default is 300000 or 5 minutes.
When an alarm occurs the services associated with that event are performed.
The alarm must reset and remain so for this amount of time before those
actions would be performed again.
SEE ALSO
HELP Topics:
$HOURMETER,
JRMON,
DIN